Resistance Area | 0,01 Ohm - 2 MOhm | 1 kOhm - 20 GOhm | 1 kOhm - 2 TOhm |
Nominal voltage | - | 100 V
250 V
500 V
1000 V | 32V
100 V
500 V
|
Test measurement current | max. 200 mA | 1 mA | - |
Continuity tester with sound | yes |
Connection / Electrode | + electrode
4 mm
- socket for
4 mm plug | + electrode
4 mm
- socket for
4 mm plug | + electrode
4 / 15 mm
- socket for
4 mm plug | + electrode
4 / 15 mm
- socket for
4 mm plug |
Power supply | 1 x 9 V |
Overvoltage category | CAT III 300 V
CAT II 600 V | CAT III 300 V
CAT II 600 V
EN/IEC 61010-1 | CAT IV 600 V
CAT III 1000 V
| CAT III 600 V
EN/IEC 61010-1 |
Protection category | IP 65 |
Ex-proofed to atex | no | yes
ll 2G
ib llC T4
DIN EN 60079-0 and
DIN EN 60079-11 | no | yes
ll 2G und l M2
ib llB T4
DIN EN 60079-0 and
DIN EN 60079-11 |
Application | Monitoring of protective measures according to EN / IEC 61557-4 (VDE 0413 part 4)
such as protective earth test or test of machine ground | Monitoring of protective measures according to
IEC 61577-2 (VDE 0413 part 2)
such as bleeder and
surface resistance tests
|
Art.-No. | 83302 | 83301 | 83315 | 83310 |
Product
Dimensions and weight | 230 x 60 x 40 mm
180 g | 230 x 60 x 40 mm
220 g | 230 x 60 x 40 mm
220 g | 230 x 60 x 40 mm
220 g |
Packed Product
Dimensions and weight | 300 x 100 x 50 mm
350 g | 300 x 100 x 50 mm
370 g | 300 x 100 x 50 mm
400 g | 300 x 100 x 50 mm
450 g |